Xnx Universal Transmitter Quick Start Guide Repack Jun 2026
Ensure the surrounding environment is free from target and interfering gases. Navigate to the Calibration Menu using the magnetic wand. Select Zero Calibration .
Wire the Alarm 1, Alarm 2, and Fault relays to the designated relay terminal block using normally open (NO) or normally closed (NC) configurations. Sensor Installation and Configuration
The screen will prompt for a security passcode. The default passcode is . Xnx Universal Transmitter Quick Start Guide
Wait for the reading to stabilize, then swipe to accept the zero point. Step 2: Span Calibration
There are four magnetic switches located around the display bezel: Up , Down , Escape (ESC) , and Enter ( ) . Accessing the Menu: Hold the magnetic wand over the Enter ( ) target for 3 seconds. Ensure the surrounding environment is free from target
: Loosen the security catch screw using an M5 hex key, then unscrew the main housing cover counter-clockwise.
: Once readings stabilize, select Confirm to save the new span factor. Wire the Alarm 1, Alarm 2, and Fault
Connect the loop receiver to terminal M-4 (Source/Sink output).
: Scroll through menus or increment numbers. Enter (ENT) : Accept a setting or enter a menu sub-level. Calibration and Testing Procedure
If you read the XNX guide, you’ll see constant references to the "4-20mA loop." In an age of Wi-Fi, 5G, and Bluetooth, it seems archaic that industrial plants still rely on a simple electrical current to transmit data.